Connect and discover
Add the approved endpoint, establish MMS association and inspect the live hierarchy, DataSets, RCBs and control model.
Use ARSAS to discover the server model, select the signals required by the test procedure, validate reporting and GOOSE behavior, inspect command completion and confirm fault-record access before equipment leaves the factory.
Adapt the sequence to the approved FAT procedure and project responsibilities.
Add the approved endpoint, establish MMS association and inspect the live hierarchy, DataSets, RCBs and control model.
Choose status, measurement, quality and timestamp points required by the test sheet instead of mapping the entire IED blindly.
Prefer configured reporting, verify exact DataSet membership and keep unsupported or unavailable coverage visible.
Check stream identity and sequence evidence, then execute only approved Direct or SBO operations with visible completion results.
Probe available fault records and retain communication, report, frame and service outcomes with the originating IED.
ARSAS does not replace calibrated injection equipment, protection-function testing, approved drawings, settings review, cybersecurity controls, witness sign-off or vendor responsibility.
Use the installer for a normal workstation, choose the portable ZIP for a controlled folder deployment, and verify the published SHA-256 before use.