Find an existing DataSet with exact coverage first.
If none exists, determine whether the IED and approved procedure permit temporary DataSet or RCB preparation. Otherwise keep the affected values in visible bounded polling.
Confirm the live member list rather than assuming the DataSet name represents the selected signals.
If none exists, determine whether the IED and approved procedure permit temporary DataSet or RCB preparation. Otherwise keep the affected values in visible bounded polling.
A name match is insufficient. The report path depends on the exact object reference, functional constraint, DataSet association and RCB configuration visible on the running device.
Confirm the data attribute and functional constraint exist in the live model.
Resolve the exact live references and compare them with the selected signals.
Check which BRCBs or URCBs reference the useful DataSet and whether they are available.
When no approved report coverage is available, show polling as polling rather than presenting it as report success.
Investigate silent reporting and RCB ownership after confirming DataSet coverage.
ARSAS can expose live model, report, GOOSE, file, control and diagnostic evidence. Final conclusions still depend on the approved project design, vendor documentation, test procedure, network access and independent verification.
Reviewed 20 July 2026 for practical IEC 61850 laboratory, FAT, SAT, commissioning and troubleshooting use.
Use the installer for a normal workstation, choose the portable ZIP for a controlled folder deployment, and verify the published SHA-256 before use.
What’s new, limitations and signing status →