Closed-loop timing authority
External TESTSET timing follows virtual BO/contact/wire/BI behavior with independent clock domains rather than direct access to relay private trip state.
Research baseline · beta.6
ARVREL now ships closed-loop feeder timing, process-bus trust, Transformer Differential, and AVR/OLTC MMS workflows. Research work therefore separates validated software behavior from future device-specific measurement and HIL evidence.
Current research contributions
External TESTSET timing follows virtual BO/contact/wire/BI behavior with independent clock domains rather than direct access to relay private trip state.
Instantaneous terminal samples, signed clipping/quantization, configured delay, settled pre-fault history, and a causal rolling measurement connect source behavior to protection timing.
Generic ANY PICKUP, TESTSET BI2, operated-element pickup/P→T, relay trip request, TESTSET BI1, frozen capture, and reset/re-arm remain distinct.
Identity, mapping/scaling, continuity, quality, complete windows, and permission gates provide a reproducible trust-before-trip model.
87T/87T-HS/REF, security, synchronized two-sided internal injection, and paired-SV external evaluation provide a current transformer research surface.
The virtual plant, 17-position OLTC, authority/interlocks, reports, and modeled MMS controls support repeatable control-system experiments without physical authority.
Technical notes
Nominal-frequency complete-window phasor estimation assumptions, evidence, and limitations.
AN-02smpCnt, duplicate/out-of-order behavior, stale windows, reset/recovery, and trust transitions.
Polarizing quantities, directional decisions, and validation boundaries for 67 functions.
Validation
Foundational process-bus scenarios plus beta.6 closed-loop metrology regressions and current release gates.
Versioned scenario IDs with source/test references for reproducible public traceability.
Standards, established engineering concepts, and external technical context without unsupported superiority claims.
Current scientific boundaries
Future evidence tracks
Measure anti-alias response, externally observable ADC behavior, channel skew, burden, BI thresholds, contact statistics, and timing uncertainty.
Expand frequency, harmonic/interharmonic, noise, decaying-DC, and CT-saturation characterization before broader accuracy claims.
Use calibrated independent timestamps and defined scheduling contracts to compare software timing with controlled hardware and deployment environments.
Claim boundary
ARVREL does not claim calibrated relay-test-set accuracy, manufacturer-specific relay equivalence, IEC 61850 conformance, IEC 60255 type testing, protection-grade hard-real-time operation, commissioning acceptance, or field-control authority.