ArSubsv separates three different measurement concepts:

  1. the raw protocol count,
  2. the profile-scaled wire engineering value,
  3. a primary or secondary-equivalent display value produced from explicit CT/VT context.

The Subscriber never derives a transformer ratio from vendor identity, signal amplitude, APPID, MAC address, or svID naming.

User workflow

  1. Select a discovered SV stream.
  2. Open CT/VT from the responsive toolbar.
  3. Declare whether the scaled value on the wire is interpreted as PrimaryEngineering or SecondaryEquivalent.
  4. Choose the preferred display domain.
  5. Enter current and/or voltage primary and secondary nominal values.
  6. Record the evidence source and reference.
  7. Apply the context.

Waveform, decoded engineering values, RMS, and phasors use the preferred domain only when the relevant ratio is valid. A missing current ratio does not prevent a verified voltage ratio from being used, and vice versa. Channels without sufficient context stay in their wire engineering domain.

JSON evidence document

Use Ctx Export to save configured contexts. Use Ctx Import to restore them or apply them before the corresponding stream is discovered.

{
  "schemaVersion": 1,
  "exportedAt": "2026-07-22T08:30:00Z",
  "streams": [
    {
      "streamKey": "logical-stream-key",
      "svId": "MU01",
      "wireDomain": "PrimaryEngineering",
      "displayDomain": "SecondaryEquivalent",
      "currentRatio": {
        "primaryNominal": 1000,
        "secondaryNominal": 1,
        "unit": "A",
        "source": "DeviceConfiguration",
        "reference": "SMU current input configuration"
      },
      "voltageRatio": {
        "primaryNominal": 20000,
        "secondaryNominal": 100,
        "unit": "V",
        "source": "DeviceConfiguration",
        "reference": "SMU voltage input configuration"
      },
      "notes": "Matched to the sanitized SCL and known-injection PCAP"
    }
  ]
}

Evidence rules

Validation boundary

The context workflow makes primary/secondary interpretation explicit and repeatable. It does not turn a Windows PC into a calibrated test set, and it does not replace device-specific injection validation.

GPL-3.0-or-later community documentation. Commercial terms require a separate agreement.Review this page on GitHub →