ARSVIN GitHub

P1 Publisher Evidence Workflow

ARSVIN remains an IEC 61850 Sampled Values publisher. P1 adds evidence features that help an engineer prove what ARSVIN intends to transmit without turning the application into a network analyzer.

What P1 adds

Intended usage

  1. Open an SCL file.
  2. Select and enable one or more IED / MU publisher slots.
  3. Set source MAC, APPID, destination MAC, VLAN, sample rate, nofASDU from SCL, dLSB, signal source, and quality mode.
  4. Click Check to review blocking errors and warnings.
  5. Click PCAP to export generated frames for offline inspection.
  6. Click Report to export the Markdown publisher evidence report.
  7. Use the report and PCAP together during lab setup, relay subscription checks, or public issue reporting.

Scope boundary

P1 does not add a subscriber, network scanner, GOOSE/SV analyzer, or live configuration-versus-wire mismatch engine. The report is generated from ARSVIN's configured TX plan and validation results.

Current limitations

Apache-2.0 engineering documentation. Edit or review this page on GitHub →