ARIEC60870 sanitized IEC-104 sample trace ========================================= Purpose ------- This sample trace is intentionally sanitized. It is not copied from a project site. Use it to explain the ARIEC60870 evidence workflow: raw traffic, readable interpretation, Smart Findings, and report output. Scenario -------- A device answers the IEC-104 session and STARTDT succeeds, but application ASDUs are returned with a different Common Address than the test profile expects. Expected profile ---------------- Protocol: IEC 60870-5-104 Endpoint: 192.0.2.10:2404 (documentation example address) Expected Common Address: 1 Workflow: STARTDT, General Interrogation, value/event review, Smart Findings, PDF report Trace summary ------------- [00:00.000] TX U-frame STARTDT activation [00:00.018] RX U-frame STARTDT confirmation [00:00.120] TX I-frame General Interrogation activation, CA=1 [00:00.166] RX I-frame activation confirmation, CA=2 [00:00.221] RX I-frame measured/status data, CA=2 [00:00.250] RX S-frame acknowledgement Readable interpretation ----------------------- The transport/session is alive because STARTDT was confirmed and I/S frame traffic is visible. The application layer does not match the expected project profile because the device answers with CA=2 while the test setup expects CA=1. Smart Finding example --------------------- Problem: Device answered, but ASDU Common Address does not match the expected profile. Proof: RX ASDU uses CA=2; configured expected CA is 1. Likely cause: Wrong station address, wrong profile, wrong endpoint, or device configuration mismatch. Next step: Verify device CA, project interoperability document, endpoint selection, and ARIEC60870 setup. Evidence report notes --------------------- Include session setup, selected trace rows, frame interpretation, Smart Findings, values/events affected by CA mismatch, and the final engineering conclusion.